FL-ECT series 303

FL-ECT 303 is a 3PH-3PH Online UPS for industrial application with regenerative load bank. Designed for harsh electrical and environmental conditions this model is a long life model.

Uninterupted power is the prime infrastructure of any business-process and a basic need of any successful sustaining operations. With the increase of atomization of process and production lines, to reduce costs, improve quality and productivity, nothing could be more expensive than the interruption of the production line due to the interruption of power. The cost of such breakdown could mean wastage of raw material, labor to set the production in place and more importantly potential damage of customer relation due to delivery delays.

Capability to handle 4-quadrant regenerative loads. (process industry).

REGENERATIVE ENERGY.

When rotating element of a motor runs faster than its voltage drive control (command), then the motor begins to act as generator and energy pumps back to the source. The conventional Online UPS cannot absorb this energy and the DC bus voltage starts increasing and leads to failure of DC capacitor and switching device.

The re-generative braking energy is produced in the following conditions,

  1. Quickly decelerating a high inertia (mechanical arm, flywheel).
  2. Controlling the speed of a load moving vertically downwards (declining conveyor)
  3. ) Sudden drop in load torque. (Drilling operation, industrial saw)
  4. Repetitive acceleration and deceleration to a stop.

Technical Specification

Note:The details given below are for FL-ECT 303 Series True online UPS of capacity 240 KVA. Certain parameters like Input Current, Charging Current etc. will vary as per the capacity.

General

. EC Series Online UPS MODEL EC 301 the winner of best in product range from SD awards 2010-11

Technology

Technology Double conversion Online with the latest MPWM technology using IGBT
DC Bus 240V
Rating 15KVA

Input

Input Frequency 50Hz ± 10%
Input Voltage 415 V AC 3 Phase & N
Input Voltage Window 330-470 V
Power walk in Soft start for 0-20 seconds power walk-in.

Efficiency

Overall Efficiency 100 % Load > 88 %

Protections

Neutral drift
Neutral failure
Lightning
EMI & Harmonics in the input neutral
High voltage transient protection & Electrostatic discharge protection as per IEC 62040-2
Galvanic isolation provides complete isolation between output neutral and Input & the the output is fully protected against neutral drifts, voltage avalanches like lighting & input harmonics commonly found in the input side.
Output short circuit with pulse by pulse current limit up to 200 micro secs.Protects 300% for 15 msecs,500% for 5 msec & 1000% for 1.5 msec of the rated current Protects against false tripping & complete shutdown in case of surge power drawn by the load (non linear loads)
Output Single Phase prevention Protects the connected three phase loads & its components from premature failure
Output Under Voltage
Output Over Voltage
Protects the load and its components from premature failure

Alarms

Input / Low / Fail
Output Overload
Over Temperature
Battery low
Alarms .

Rectifier

Converter Protection Advanced Electronic Protection for device safety backed up with MCB's & fast acting fuses
Ripple Voltage < 2%
Type IGBT based full bridge
Voltage Regulation (±) 1%

Inverter

Crest Factor 3:1
Frequency 50Hz ± 0.1Hz
Inverter Type IGBT based MPWM with instantaneous Sinewave Control
Mode of Operation Designed for Continuous operation
Nominal output Current 52A
Nominal Voltage 230VAC Single Phase
Over Load Capacity 100 % Load Continuous
125 % Load 1 Minute
150 % Load 10 Seconds
Power Factor 0.8 lag
Regulation (±) 1%
Total Harmonic Distortion Linear Load < 2%
Non Linear Load < 6%
Transient Response Remains within ± 5% & recover to normal within 20 msec
Waveform True Sinewave

Isolation

Inverter Protection Advanced Electronic Protection for device safety backed up with MCB's & fast acting fuses, high speed pulse by pulse electronic device protection over voltage / under voltage protection, Electronic over current trip with reset.
Isolation True Online with complete galvanic isolation.

Bypass

Manual Bypass Provided
Static bypass(Optional)

Battery

Battery Low advance warning at 220V
Battery Low cut off at 210V
Battery Type SMF/ Tubular
Charger Type CVCC
Charging Current Standard 1-6 A
Voltage 12V x 20-240VDC

Environmental

Acoustic Noise level <60db @ 1.5 meter
Altitude < 3000 Feet above sea level (without derating)
Ambient Temperature 0 to 40 Deg C
Extreme climatic conditions AC Environment is required if the temperature goes beyond the normal operating temperature (0-40 deg C)
Humidity Up to 95% RH Non condensing
Storage Temperature -10 to 70 Deg C

Physical

Cable Entry Front side bottom
Cooling Forced Air
Dimensions in mm - D X H X W & Weight (approximate) 760 x 785 x 390 - 130 Kg
Enclosure Protection Grade IP - 20
Testing Standard As per IEC 62040 - 3
Comments
Manufacturer: 

About SEMED

For years now, SEMED has been providing a full range of Medical Equipment solutions across all level of Healthcare providers in Nigeria, with strong and efficient After-sales service support. Its globally-recognized products reduce healthcare costs with reliableRead More

Contact Info

  • This email address is being protected from spambots. You need JavaScript enabled to view it.">Contact Sales
  • This email address is being protected from spambots. You need JavaScript enabled to view it.
  • This email address is being protected from spambots. You need JavaScript enabled to view it.